Instrumentation · Lesson 1 of 10
Every machine in a plant needs to sense (temperature, pressure, weight, speed), then decide, then act. Instrumentation is the part that senses and passes that information to the PLC. In this lesson you will understand the whole loop, run a real heating loop yourself, and learn to read the tags on drawings and devices.
Think of it like this: the sensor is like your hand feeling that the water is hot, the PLC or controller is like the brain deciding "that's too hot", and the valve or motor is like your other hand turning off the tap. Without the sensing, the brain can't do anything.
| Term | Meaning | Example in the heating tank |
|---|---|---|
| PV Process Variable | The actual value we are measuring now | Temperature 63 °C |
| SP Set Point | The value you want | 70 °C |
| Error | The difference: SP − PV | 7 °C |
| OUT / MV Output | The controller's command to the actuator (0–100 %) | Valve 65 % open |
This is a water tank heated by steam. TT-101 measures the temperature and sends 4–20 mA to the controller TIC-101, and the controller opens and closes the steam valve TV-101. Move the SP, try Manual, and open the cold water to see how the controller reacts. (Time here runs 8 times faster than real life.)
Every transmitter is set to a range: the lowest value (LRV, Lower Range Value) gives 4 mA, and the highest value (URV, Upper Range Value) gives 20 mA. The span = URV − LRV.
| Term | Meaning | Example |
|---|---|---|
| Accuracy | How close the reading is to the truth | ±0.1 % of span ⇒ on a 0–150 °C range that is ±0.15 °C |
| Resolution | The smallest change the device can show | The display shows 0.1 °C |
| Repeatability | Gives the same reading when measuring the same thing several times | ±0.05 % |
An important rule: choose a range that fits the job. A pressure transmitter with a 0–100 bar range working at 3 bar has an accuracy of ±0.1 % of 100 = ±0.1 bar, so the error could be 3 % of your reading!
On P&ID drawings (piping and instrumentation diagrams) and on the nameplate of every device in the field, each instrument has a tag following ISA-5.1: the first letter = what is measured, the following letters = the device's function, and then the loop number.
| First letter | Measures |
|---|---|
| T | Temperature |
| P | Pressure |
| F | Flow |
| L | Level |
| W | Weight |
| S | Speed |
| Z | Position |
| Next letters | Function |
|---|---|
| T | Transmitter |
| E | Element (the sensor itself) |
| I | Indicator (display / gauge) |
| C | Controller |
| S | Switch |
| V | Valve |
| A · H · L | Alarm · high · low |
| D (after the first) | Differential |
Get at least 5 of 6 right to mark the lesson as done.
Tagging follows ISA-5.1; some plants use their own numbering system (KKS, for example). Your progress is saved on this device only.