VFD course · Lesson 2 of 12
From the outside a VFD is a box with a display and terminals. Inside it is 3 stages in a row: it turns AC into DC, stores it, then chops it up fast to make new AC exactly the way we want. Understand these stages and you will understand every VFD fault after this.
Tap each part of the drawing, and change the supply voltage to see how the DC bus voltage changes. Under each part is the waveform at that point.
The capacitors charge almost to the peak of the wave. On three phase, under load, the well-known figure is:
| Supply | DC bus, roughly |
|---|---|
| Single phase 230 V | ≈ 325 V (230 × 1.41) |
| 3 phase 400 V | ≈ 540 V (with no load it can reach 565 V) |
| 3 phase 480 V | ≈ 650 V |
Get at least 5 of 6 right to complete the lesson.
The numbers and examples here are common training values, and parameter and terminal names differ from brand to brand and model to model: your drive's manual is the reference. Your progress is saved on this device.